HomeQuienes SomosProductosCapacidadesCalidadContactenosPublicacionesLicores

ID:

Español  

Password:

 


Wires - Galvanized for ACSR Conductor Centers



With the rapid development of electrical generator plants, the ACSR (Aluminum Conductor Steel Reinforced) presents itself as the perfect cable for the transmission of electricity. The galvanized strand for ACSR requires a great quality due to the fact that they constitute the support for aluminum conductors across great distances.

This Wire is cold drawn and then covered with Zinc, achieving the customer’s desired properties.

Chemical Composition

Element

Composition %

Carbon

0.50 to 0.85

Magnesium

0.50 to 1.10

Phosphorus

0.035

Sulfur

0.045

Silicon

0.10 to 0.35


Dimensions and Permissible Variations

Nominal Diameter

Effort at  1% minimum extension

Minimum Resistance Limit to Tension

Minimum Stretching to the break point in 10 inches or 250 mm %

Inches

ksi

Ksi

 

 

Covering

CLASS A

 

0,0500 to 0,0899

190

210

3,0

0,0900 to 0,1199

185

205

3,5

0,1200 to 0,1399

180

205

4,0

0,1400 to 0,1900

170

200

4,0

 

Covering

CLASS B

 

0,0500 to 0,0899

180

200

3,0

0,0900 to 0,1199

175

195

3,0

0,1200 to 0,1399

170

195

3,0

0,1400 to 0,1900

160

185

4,0

 

Covering

CLASS C

 

0,0500 to 0,0899

170

190

3,0

0,0900 to 0,1199

165

185

3,0

0,1200 to 0,1399

160

185

3,0

0,1400 to 0,1900

155

180

4,0


Minimum Density of the Covering area

Inches

CLASS A

CLASS B

CLASS C

0,0500 a 0,0599

0,60

1,20

1,80

0,0600 a 0,0749

0,65

1,30

1,95

0,0750 a 0,0899

0,70

1,40

2,10

0,0900 a 0,1059

0,75

1,50

2,25

0,1040 a 0,1199

0,80

1,60

2,40

0,1200 a 0,1399

0,85

1,70

2,55

0,1400 a 0,1799

0,90

1,80

2,70

0,1800 a 0,1900

1,00

2,00

3,00

Millimeters

 

 

 

1,60 a 1,90

210

420

630

1,90 a 2,30

220

440

660

2,30 a 2,70

230

460

690

2,70 a 3,10

240

480

720

3,10 a 3,50

260

520

780

3,50 a 3,90

270

540

810

3,90 a 4,50

275

550

825

4,50 a 4,80

300

600

900

 

Tension Requisites

Nominal Diameter

Effort at  1% minimum extension

Minimum Resistance Limit to Tension

Minimum Stretching to the break point in 10 inches or 250 mm %

Inches

Ksi

Ksi

 

CLASS A

 

 

 

0.0500 to 0.0899, inclusive

190

210

3,0

0.0900 to 0.1199, inclusive

185

205

3,5

0.1200 to 0.1399, inclusive

180

205

4,0

0.1400 to 0.1900, inclusive

170

200

4,0

CLASS B

 

 

 

0.0500 to 0.0899, inclusive

180

200

3,0

0.0900 to 0.1199, inclusive

175

195

3,0

0.1200 to 0.1399, inclusive

170

195

3,0

0.1400 to 0.1900, inclusive

160

185

4,0

CLASS C

 

 

 

0.0500 to 0.0899, inclusive

170

190

3,0

0.0900 to 0.1199, inclusive

165

185

3,0

0.1200 to 0.1399, inclusive

160

185

3,0

0.1400 to 0.1900, inclusive

155

180

4,0


Tension Requisites

Nominal Diameter

Effort at  1% minimum extension

Minimum Resistance Limit to Tension

Minimum Stretching to the break point in 10 inches or 250 mm %

Millimeters

MPa

MPa

 

CLASS A

 

 

 

1.60 to 2.30, inclusive

1310

1450

3,0

2.30 to 3.05, inclusive

1280

1410

3,5

3.05 to 3.60, inclusive

1240

1410

4,0

3.60 to 4.80, inclusive

1170

1380

4,0

CLASS B

 

 

 

1.60 to 2.30, inclusive

1240

1380

3,0

2.30 to 3.05, inclusive

1210

1340

3,0

3.05 to 3.60, inclusive

1170

1340

3,0

3.60 to 4.80, inclusive

1100

1280

4,0

CLASS C

 

 

 

1.60 to 2.30, inclusive

1170

1310

3,0

2.30 to 3.05, inclusive

1140

1280

3,0

3.05 to 3.60, inclusive

1100

1280

3,0

3.60 to 4.80, inclusive

1070

1240

4,0

 







EMCOCABLES S.A. Km. 5.5 Vía Cajica – Zipaquira Tel 57 (1) 3766030 - © 2005