Wires - Galvanized for ACSR Conductor Centers
With the rapid development of electrical generator plants, the ACSR (Aluminum Conductor Steel Reinforced) presents itself as the perfect cable for the transmission of electricity. The galvanized strand for ACSR requires a great quality due to the fact that they constitute the support for aluminum conductors across great distances.
This Wire is cold drawn and then covered with Zinc, achieving the customer’s desired properties.
Chemical Composition
Element |
Composition % |
Carbon |
0.50 to 0.85 |
Magnesium |
0.50 to 1.10 |
Phosphorus |
0.035 |
Sulfur |
0.045 |
Silicon |
0.10 to 0.35 |
Dimensions and Permissible Variations
Nominal Diameter |
Effort at 1% minimum extension |
Minimum Resistance Limit to Tension |
Minimum Stretching to the break point in 10 inches or 250 mm % |
Inches |
ksi |
Ksi |
|
|
Covering |
CLASS A |
|
0,0500 to 0,0899 |
190 |
210 |
3,0 |
0,0900 to 0,1199 |
185 |
205 |
3,5 |
0,1200 to 0,1399 |
180 |
205 |
4,0 |
0,1400 to 0,1900 |
170 |
200 |
4,0 |
|
Covering |
CLASS B |
|
0,0500 to 0,0899 |
180 |
200 |
3,0 |
0,0900 to 0,1199 |
175 |
195 |
3,0 |
0,1200 to 0,1399 |
170 |
195 |
3,0 |
0,1400 to 0,1900 |
160 |
185 |
4,0 |
|
Covering |
CLASS C |
|
0,0500 to 0,0899 |
170 |
190 |
3,0 |
0,0900 to 0,1199 |
165 |
185 |
3,0 |
0,1200 to 0,1399 |
160 |
185 |
3,0 |
0,1400 to 0,1900 |
155 |
180 |
4,0 |
Minimum Density of the Covering area
Inches |
CLASS A |
CLASS B |
CLASS C |
0,0500 a 0,0599 |
0,60 |
1,20 |
1,80 |
0,0600 a 0,0749 |
0,65 |
1,30 |
1,95 |
0,0750 a 0,0899 |
0,70 |
1,40 |
2,10 |
0,0900 a 0,1059 |
0,75 |
1,50 |
2,25 |
0,1040 a 0,1199 |
0,80 |
1,60 |
2,40 |
0,1200 a 0,1399 |
0,85 |
1,70 |
2,55 |
0,1400 a 0,1799 |
0,90 |
1,80 |
2,70 |
0,1800 a 0,1900 |
1,00 |
2,00 |
3,00 |
Millimeters |
|
|
|
1,60 a 1,90 |
210 |
420 |
630 |
1,90 a 2,30 |
220 |
440 |
660 |
2,30 a 2,70 |
230 |
460 |
690 |
2,70 a 3,10 |
240 |
480 |
720 |
3,10 a 3,50 |
260 |
520 |
780 |
3,50 a 3,90 |
270 |
540 |
810 |
3,90 a 4,50 |
275 |
550 |
825 |
4,50 a 4,80 |
300 |
600 |
900 |
Tension Requisites
Nominal Diameter |
Effort at 1% minimum extension |
Minimum Resistance Limit to Tension |
Minimum Stretching to the break point in 10 inches or 250 mm % |
Inches |
Ksi |
Ksi |
|
CLASS A |
|
|
|
0.0500 to 0.0899, inclusive |
190 |
210 |
3,0 |
0.0900 to 0.1199, inclusive |
185 |
205 |
3,5 |
0.1200 to 0.1399, inclusive |
180 |
205 |
4,0 |
0.1400 to 0.1900, inclusive |
170 |
200 |
4,0 |
CLASS B |
|
|
|
0.0500 to 0.0899, inclusive |
180 |
200 |
3,0 |
0.0900 to 0.1199, inclusive |
175 |
195 |
3,0 |
0.1200 to 0.1399, inclusive |
170 |
195 |
3,0 |
0.1400 to 0.1900, inclusive |
160 |
185 |
4,0 |
CLASS C |
|
|
|
0.0500 to 0.0899, inclusive |
170 |
190 |
3,0 |
0.0900 to 0.1199, inclusive |
165 |
185 |
3,0 |
0.1200 to 0.1399, inclusive |
160 |
185 |
3,0 |
0.1400 to 0.1900, inclusive |
155 |
180 |
4,0 |
Tension Requisites
Nominal Diameter |
Effort at 1% minimum extension |
Minimum Resistance Limit to Tension |
Minimum Stretching to the break point in 10 inches or 250 mm % |
Millimeters |
MPa |
MPa |
|
CLASS A |
|
|
|
1.60 to 2.30, inclusive |
1310 |
1450 |
3,0 |
2.30 to 3.05, inclusive |
1280 |
1410 |
3,5 |
3.05 to 3.60, inclusive |
1240 |
1410 |
4,0 |
3.60 to 4.80, inclusive |
1170 |
1380 |
4,0 |
CLASS B |
|
|
|
1.60 to 2.30, inclusive |
1240 |
1380 |
3,0 |
2.30 to 3.05, inclusive |
1210 |
1340 |
3,0 |
3.05 to 3.60, inclusive |
1170 |
1340 |
3,0 |
3.60 to 4.80, inclusive |
1100 |
1280 |
4,0 |
CLASS C |
|
|
|
1.60 to 2.30, inclusive |
1170 |
1310 |
3,0 |
2.30 to 3.05, inclusive |
1140 |
1280 |
3,0 |
3.05 to 3.60, inclusive |
1100 |
1280 |
3,0 |
3.60 to 4.80, inclusive |
1070 |
1240 |
4,0 |
EMCOCABLES S.A.
Km. 5.5 Vía Cajica – Zipaquira Tel 57 (1)
3766030 - © 2005
|
|
|